Energy & environment / FREE BROWSER TOOL

Simple building heat loss.

Add steady conduction through supplied U-value surfaces and a simple ventilation sensible-heat allowance.

YOUR EVERYDAY DESKKeep your
next task close.
Switch between tools ↗
Simple building heat loss
See result ↓● Live result
01 / YOUR INPUTS

Use separate rows for walls, glazing, roof, floor and other non-overlapping surfaces.

Processed on this device.

02 / YOUR RESULT

Your answer

ON YOUR DEVICE

Your result will appear here.

Adjust a field to calculate.

LOCAL INPUTS / CLEAR WORKING / USEFUL OUTPUTNothing to sign in to.

Built and maintained by Operance Labs · Report a calculation or documentation issue

A LITTLE KNOW-HOW

How to use
this tool.

  1. Enter the physical quantities using the units printed beside each field.
  2. Set efficiencies, material properties and allowances from your own measured or manufacturer data.
  3. Review the result breakdown and the stated model assumptions.

What the inputs mean

Surfaces · U-value W/(m²·K), area m²
Use separate rows for walls, glazing, roof, floor and other non-overlapping surfaces.
Inside–outside temperature difference (K or °C)
Enter inside–outside temperature difference (k or °c).
Heated internal air volume (m³)
Enter heated internal air volume (m³).
Air changes per hour
Enter air changes per hour.
Volumetric air heat capacity (Wh/m³·K)
Enter volumetric air heat capacity (wh/m³·k).
A WORKED STARTING POINT

See the working.

Inputs used in this example

These are example values, not a current price, tariff or personal recommendation. Reset example restores them in the workspace.

InputExample value
Surfaces · U-value W/(m²·K), area m²0.3, 100 1.4, 20
Inside–outside temperature difference (K or °C)20
Heated internal air volume (m³)250
Air changes per hour0.5
Volumetric air heat capacity (Wh/m³·K)0.33

Steady sensible heat loss

1,985 W

heat loss W = ΔT × (Σ(U × A) + volume × air changes/hour × air heat capacity Wh/(m³·K))

  • Conduction: 1160 W; ventilation: 825 W; combined heat-loss coefficient: 99.25 W/K.
  • No thermal bridges unless included in effective U-values. Excludes transient thermal mass, solar/internal gains, latent moisture, heat recovery and changing weather. Not a full heating-system design.

Add steady conduction through supplied U-value surfaces and a simple ventilation sensible-heat allowance.

Scenario estimates use your supplied prices, efficiencies and conditions.

Your inputs stay here

Your input is processed on this device. PixelDesk does not upload it to a calculation or file-processing server. Copying and downloading are deliberate actions. Closing the page clears the in-memory inputs; the app remembers only its theme and public reference-rate cache.

Methods and public data ↗

Keep a useful
thing close.

All energy & environment ↗

Questions, answered.

What can I do with simple building heat loss?

Add steady conduction through supplied U-value surfaces and a simple ventilation sensible-heat allowance.

What does the simple building heat loss example show?

With Surfaces · U-value W/(m²·K), area m²: 0.3, 100 1.4, 20; Inside–outside temperature difference (K or °C): 20; Heated internal air volume (m³): 250, the example returns 1,985 W. The workspace shows the substituted formula and its assumptions; Reset example restores these inputs.

What should I check before using the result?

Add steady conduction through supplied U-value surfaces and a simple ventilation sensible-heat allowance.